9
- It should always have the same diameter. It is recommended that it be circular, and never any
narrower than the boiler outlet.
-
It is obligatory to install a fume inspection plate with condensation collection, to remove
the condensation generated in the flue.
Otherwise, the condensation may reach the inside of
the boiler and cause irreparable damage,
which would not be covered
by DOMUSA TEKNIK's
guarantee.
The condensation pipe should lead to a drain outlet
, as a large amount of water
may be generated. This connection must be made in compliance with the regulations for
draining off condensation water to the drain system.
-
It is recommended that a draught stabiliser
be installed to prevent any pressure drop
variations in the flue due to atmospheric conditions, which could affect correct boiler
combustion.
This draught stabiliser must be installed below the fume inspection plate to
prevent any leakage of combustion gases.
3.7
Electrical Connection
The
Lignum NG
boiler must be connected to 230 V~ ac 50 Hz by the connector labelled
“
220V AC
”
on the back of the boiler.
The socket should have an appropriate earth connection.
The circulating pump must be connected to the 3-pin connector
“
”
on the back of the boiler,
on the side opposite the connection to the mains electrical supply.
3.7.1
DHW tank electrical connection (optional).
If there is an optional DHW tank, connect the DHW 3-way diverter valve in the 3-pin connector
“
”
. Connect the DHW temperature sensor in the controller, as indicated in the
"Electrical
Diagram"
.
The hydraulic installation for the 3-way DHW diverter valve should be made so that the heating
circuit (buffer tank) can flow through the valve when it is idle (not powered):
HEATING
BOILER
DHW
NA / NO
NC
V3V
Summary of Contents for LIGNUM NG 20
Page 1: ...INSTALLATION AND OPERATING INSTRUCTIONS LIGNUM NG ...
Page 36: ...Lignum NG 34 Outside ...
Page 42: ...Lignum NG 40 NOTES ...
Page 43: ...41 NOTES ...