BIOCLASS iC DX
20.3
Low pressure lock-out
When this lock-out occurs,
“E19”
alarm code will appear on the digital display. The burner and the
boiler's circulation pumps will switch off, cutting off the heating and water flow to the installation.
The blockage occurs when the boiler pressure drops below 0.5 bar, preventing it from working when
the installation is drained of water, either due to a leak or due to maintenance operations. To unblock
this alarm, the installation must be filled again (see "Filling the boiler"), until a pressure between 1 and
1.5 bar is displayed in the "water pressure" parameter of the "User Menu".
21
SHUTTING DOWN THE BOILER
Press
during 1 second to shut down the boiler. When the boiler is shut down the heating and DHW
services are switched off but anti-frost and pumps anti-lock functions continue activated whereas the
boiler is kept connected to the power supply and fuel installation.
Unplug the boiler from the power supply and cut out the fuel supply to shut down the boiler completely.
22
EMPTYING THE BOILER
Use the drain cock located on the bottom of the backside of the boiler to empty it of water. Before opening
it, connect a flexible pipe leaded to a sewer. After finishing the procedure, close the cock and remove de
flexible pipe.