EN
70
BIOCLASS iC DX
27
TECHNICAL DATA
MODEL
BioClass iC
DX 18
BioClass iC
DX 25
Rated heat output (Pח)
kW
17,6
24,8
Efficiency at maximum heat output
%
(NCV)
92,1
92,2
Minimum heat output (Pp)
kW
5,2
6,9
Efficiency at minimum heat output
%
(NCV)
90,3
90,4
CO at maximum heat output (10% O
2
)
mg/m
3
33
32
OGC (organic gaseous substances) at maximum heat
output (10% O
2
)
mg/m
3
1
0
Particles content at maximum heat output (10% O
2
)
mg/m
3
10
12
CO at minimum heat output (10% O
2
)
mg/m
3
56
41
OGC (organic gaseous substances) at minimum heat
output (10% O
2
)
mg/m
3
2
3
Partial load dust content (10% O
2
)
mg/m
3
4
6
Boiler class (according to EN 303-5)
-
Class 5
Maximum operating pressure
bar
3
Maximum operating temperature
ºC
80
Maximum safety temperature
ºC
110
Water volume
litros
178
224
Minimum flue draught
mbar
0,05
Maximum flue draught
mbar
0,20
Flue gas mass flow rate at nominal/partial load
Kg/s
0,013/0,005
0,018/0,006
Flue gas temperature at nominal/partial load
ºC
140/90
Electrical supply
-
230 V~, 50 Hz, 2,50 A
Boiler chimney diameter
mm
100
100
Maximum water content of the fuel
%
7
Minimum return temperature
ºC
25 ºC
Water pressure drop (dT = 20 K)
mbar
63
130
Noise level (according to 15036-1)
dB
56
56
Weight (net)
Kg
290
370