BioClass TR
62
28
TECHNICAL DATA
MODEL
BioClass
TR 10
BioClass
TR 16
BioClass
TR 25
Maximum heat output
kW
10,1
15,6
25,3
Efficiency at maximum heat output
%
93,5
93,5
95
Minimum heat output
kW
2,9
4,2
6,9
Efficiency at minimum heat output
%
89,5
88,5
92
CO at maximum heat output (10% O
2
)
mg/m
3
110 120 45
OGC (organic gaseous substances) at
maximum heat output (10% O
2
)
mg/m
3
7 6 <5
Particles content at maximum heat
output (10% O2)
mg/m
3
25 25 20
CO at minimum heat output (10% O
2
)
mg/m
3
250 460 240
OGC (organic gaseous substances) at
minimum heat output (10% O
2
)
mg/m
3
15 20 5
Boiler class (according to EN 303-5)
-
Class 5
Maximum operating pressure
bar
3
Maximum operating temperature
ºC
110
Water volume
l
46
55
73
Minimum flue draught
mbar
0,10
Maximum flue draught
mbar
0,20
Electrical supply
-
230 V~, 50 Hz, 1.5 A
Boiler chimney diameter
mm
125
125
150
Fuel -
Olive stone /
6-8 mm wood pellet.
Maximum length 35 mm.
Maximum water content of the fuel
%
7
Minimum return temperature
ºC
25 ºC
Water pressure drop (dT = 20 K)
mbar
30
70
140
Stand by power
W
7
Weight (net)
Kg
190
211
300