BioClass TR
64
2-Variable differential pressure (
∆
p-v):
The setpoint value of the differential pressure H increases in a straight line between ½H and H
within the permitted flow margin. The differential pressure generated by the pump is
adjusted to the appropriate setpoint value of differential pressure.
Min.
As well as the hydrodriving pressure of the pump, it is essential to consider the pressure drop of the
installation to assure the correct sizing up of the hydraulic installation. The following diagram
shows the pressure drop for each model of
BioClass TR
boiler.
Pressure drop
0
1
2
3
4
5
6
7
0
0,5
1
1,5
2
2,5
Q(m
3
/h)
H(m)
TR 10
TR 16
TR 25