When the “Local/Remote” selection
switch is set at “Remote” position, the
start/stop of the fan motor can be
controlled remotely. When the remote
control switch is closed the “Running”
green indication light will light up and the
fan motor will be powered up; when the
remote control switch is opened the
“Running” green indication light will go off,
and the fan motor dis-energized.
When the "Local/Remote" selection
switch is set at "Local" position all control
operations need to be carried out locally
at the control panel. The fan motor can
be turn on and off by pushing the "Fan
Start" and "Fan Stop" buttons
respectively. When push the “Fan Start
“
button, the “Running” green
indication light will light up and the fan
motor will be powered up; when push the
“Fan Stop” button the “Running” green
indication light will go off and the fan
motor dis-energized.
When the "Auto/Manual" selection switch
is set at "Manual" position, the cleaning
will process continually. When the
"Auto/Manual" selection switch is set at
"Auto" position the cleaning will be
controlled by the Torit Delta P-C01
controller on the panel. At any time
the cleaning pulse is activated, the
“Cleaning” indication light on the panel
will light up.
There is overload protection for the fan
motor, the setting of AMPs according to
the nameplate of the fan motor. When the
"Error" indication light lights up it signifies
that the fan motor is overloaded and has
stopped.
To terminate electrical power supply to
the pulsing control, please ensure that
the fan motor is shut down before turning
the main power supply switch to the
"OFF" position.