Torit PowerCore, TG 2 to TG 12
10
1. Remove the plastic pipe plug from the collector’s air
manifold and connect the compressed-air supply
lines. Use thread-sealing tape or pipe sealant on all
compressed-air connections.
2. Install a customer-supplied shut-off valve, bleed-
type regulator with gauge, filter, and automatic
condensate valve in the compressed-air supply line.
3. Set compressed-air supply to 90-psig. The pulse-
cleaning controls are factory set to clean one filter
pack every 10-seconds during each cleaning cycle
on the TG2 through TG8 and two filter packs every
10-seconds on the TG12.
air regulator*
bleed-type air filter*
automatic
condensate valve*
air supply line*
safety exhaust
valve*
*customer-supplied
Turn power off and lock out
electrical power sources.
Turn compressed air supply OFF, bleed
and lock out lines before performing
service or maintenance work.
Compressed Air Installation
Compressed Air Installation
Turn compressed air supply OFF,
bleed and lock out lines before
performing service or maintenance work.
A safety exhaust valve should be used to
isolate the compressed air supply. The safety
exhaust valve should completely exhaust
pressure in the collector manifolds when
closed, should be capable of being interlocked
with fire or explosion mitigation equipment
and should include provisions to allow closed-
position locking.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100-psig
supply pressure.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed-air lines to remove
debris before connecting to the collector’s
compressed-air manifold.