13
(5) Power Source Facility
DANGER
Without plug and outlet, you can connect the line directly to R.S.T. 3
phases line. In this case, the skilled electric engineer must connect. If
not, you may hurt or die by the electricity shock.
Please check the using voltage supply is appropriate with the machine
’
s 3
phases voltage. The voltage is written on the Power Switch of the control
panel.
The power can be connected under the condition that the volume of
breaker of factory should be more than 20A. Please connect power line over
2.0mm 2 with 4 core wire with tunnel of breaker.
♦
Please connect ground wire before connecting power line.
♦
Please wear the safety glove and be off the power before connecting
power line.
♦
When operating the hydraulic pump motor, you must check if the
direction of motor rotation is as same as arrow direction of the cover of
hydraulic pump, if the direction isn’t same, the pump can be damaged
only after 10 seconds movement. If the direction is not same, please
exchange the 2 wires out of 3 wires of motor.