CPRS-1400,1400D INSTALLATION MANUAL
Issue : 2004.07
ED : 0
CPRS-1400,1400D INSTALLATION MANUAL 34 /47
Table 4. Output Cable Connection Bolts & Nuts
LOAD GND
(RETURN)
45mm, 2HOLE LUG
Î
BOLT : M8, hexa BOLT, 25mm
22mm, 2HOLE LUG
Î
OLT : M8. 20mm
45mm, 2HOLE LUG
Î
BOLT : M8, hexa BOLT, 25mm
22mm, 2HOLE LUG
Î
BOLT : M8. 20mm
3.3.13 Battery Cable Connection & Fuse Location
Caution : Battery should be connected when all other cables have been
connected.
Before connecting the battery, fuse and the alarm fuse should be taken apart. And
set open the LVD OPEN/NORMAL switch of the control panel. Once the cabling is
completed, put the fuse to the original place, and then insert the alarm fuse.
Battery fuse should be rated (800Ax2EA) TPH type.
B+
B) (RETURN BUSBAR)