CPRS-1400,1400D INSTALLATION MANUAL
Issue : 2004.07
ED : 0
CPRS-1400,1400D INSTALLATION MANUAL 9 /47
•
Battery Fuse : 800A
×
2EA
5)Stability of input and load :
±
1.0%(0.54V)
6)Output current limitation : at 40
%
∼
110
%
7)Output over voltage protection : Suspend rectifier module at 59.0V
∼
60V.
8)Battery over discharge protection : Suspend battery at 42.0V
±
0.2V.
9)Output Ripple / Noise : - 250mV or less at peat point
1.2 Safety Specifications
1.2.1 Electro Magnetic Interference (EMI)
Î
FCC PART 15 SUBPART B, CLASS A
- 450kHz
≤
f
≤
1.6MHz : 1mV (60dB
㎶
) or lower
- 1.6MHz
≤
f
≤
30MHz : 3mV (69.5dB
㎶
) or lower
1.2.2 Surge Voltage of Power Cable
Î
Voltage
→
6kV (1.2
×
50
㎲
), Current
→
3kA (8
×
20
㎲
)
1.2.3 Leaked Current
Î
100mA or lower
1.3 Environmental Characteristics
1.3.1 Operating Temperature & Humidity
-20
℃
∼
+50
℃
, 10%
∼
90%
1.3.2 Storage Temperature & Humidity
-40
℃
∼
+80
℃
, 5%
∼
95%
1.4 Physical Specifications
1.4.1 Dimension
: 1800(H) X 750(W) X 700(D) ( mm )