VPRS-4175E OPERATION MANUAL
Issue : 2009.03
ED : 1
VPRS-4175E OPERATION MANUAL 32 /31
7.6 Rectifier Module Restart
7.6.1 When Module is Shut Down by Over Voltage
If output voltage is suspended due to OV, and then fully shut down due to
regeneration in 5 minutes, manually set off the switch on the front panel to
standby location, and then set on the switch to ON location.
7.6.2 Rectifier Unit Thermal Shut Down
If internal temperature of the unit hikes, the unit will be shut down by its
protection circuit. To restore the module, push the switch at the rectifier unit front
to OFF and then push the switch again to ON manually.
7.7
Battery Charge Current Limitation
This function enables user to set ON or OFF. Default is OFF. In that case, the
maximum value of charge current equals the output current limit of rectifier, which
means max current limit of the installed rectifier modules. (See Table 5.)
7.8
Control Panel Power Drop
If power of the rectifier system falls below 42.0V due to commercial power failure,
all of the control panel functions will be suspended. However, all of set values will
be maintained.
8 Control Panel Setup & Measurement