VPRS-430 OPERATION MANUAL
Issue : 2009.03
ED : 1
VPRS-430 OPERATION MANUAL 11 /30
7)Output over voltage protection : Suspend rectifier module at 59.0V
∼
60.0V.
8)Battery over discharge protection : Suspend battery at 42.0V
±
0.2V.
9)Output Ripple / Noise : 100mV or less at peat point
1.2 Safety Specifications
1.2.1 Electro Magnetic Interference (EMI)
Î
FCC PART 15 SUBPART B, CLASS A
- 450kHz
≤
f
≤
1.6MHz : 1mV (60dB
㎶
) or lower
- 1.6MHz
≤
f
≤
30MHz : 3mV (69.5dB
㎶
) or lower
1.2.2 Surge Voltage of Power Cable
Î
Voltage
→
6kV (1.2
×
50
㎲
), Current
→
3kA (8
×
20
㎲
)
1.2.3 Leaked Current
Î
10mA or lower
1.3 Environmental Characteristics
1.3.1 Operating Temperature & Humidity
-10
℃
∼
+55
℃
, 10%
∼
95%
1.3.2
Storage Temperature & Humidity
-40
℃
∼
+80
℃
, 5%
∼
95%
1.4 Physical Specifications
1.4.1 Dimension
VPRS-430 Rectifier Shelf
⇒
132.5(H) X 482.6(W) X 396.2(D) ( mm )
VPRM5415 Rectifier Module
⇒
130(H) X 65(W) X 331(D) ( mm )
1.4.2 Weight
VPRS-430 Shelf
⇒
11 Kg (w/o 2 rectifier modules)