VPRS-430 OPERATION MANUAL
Issue : 2009.03
ED : 1
VPRS-430 OPERATION MANUAL 21 /30
CLASSIFICATION
AVAILABLE RANGE
DEFAULT
FL Voltage
-44.0 ~ -59.0V
-54.5V
EQ Voltage
-44.0 ~ -59.0V
-56.0V
AC INPUT OV/UV ALARM
Fixed Value
291Vac / 89Vac
AC INPUT OV/UV S/D
Fixed Value
296Vac / 84Vac
DC OUTPUT OV/UV
-48.0 ~ -59.0V , -42.0 ~ -52.0V
-57.0V / -43.0V
Output Current Limit
40% (when input voltage is 180V or less)
105% (when input voltage is 190V or higher)
40% or 105%
Battery Charge Current Limit
OFF/ 10A ~ 200A
60A
Battery Charge Current
10A ~ 200A
50A
Battery Charge End Current
2A ~ 100A
5A
Temp Mode
ON/OFF
ON
Battery Charge Slect
Auto
Manual (FL MODE/EQ MODE)
Auto
Battery Emergency Voltage
-42.0V ~ -48.0V
-44.0V
5.3
Control Panel Operation
See Control Panel Operation Manual.
6
Manual Battery Disconnect
Manual BATTERY DISCONNECT switch : C/B(Circuit Breker) type located at the
rear side of the front panel. When the C/B is in ON position, it connects the battery to
the rectifier and the system. (Rectifier is normal and output voltage is 46V or higher.)
Normal operation state.
When it is in OFF position, it separates the battery from the rectifier and the system.
(When battery is repaired or replaced.)