VPRS-430 OPERATION MANUAL
Issue : 2009.03
ED : 1
VPRS-430 OPERATION MANUAL 23 /30
operate in temperature compensation mode. If the Temp saner probe is taken out,
TEMP OUT is displayed and temperature compensation will not operate. Then, the
system will return to the operator defined mode (FL/EQ).
* FL Charge Mode
5 6 . 4 V
5 2 . 8 V
0 ℃
5 ℃
3 2 ℃
T e m p
V o u t
- 1 0 ℃
A c t u a l T e m p e ra t u re C o rre c t e d V o lt a g e
2 . 2 0 V / C e ll
2 . 2 4 V / C e ll
2 . 3 0 V / C e ll
2 . 3 5 V / C e ll
3 2 ℃ ( 9 0 F ) o r a b o v e
2 5 ℃ ( 7 7 F )
1 5 ℃ ( 5 9 F )
5 ℃ ( 4 0 F ) o r b e lo w
Figure 8. BTC-FL MODE
* EQ Charge Mode
5 6 . 4 V
5 2 . 8 V
0 ℃
2 5 ℃
5 2 ℃
T e m p
V o u t
- 1 0 ℃
A c t u a l T e m p e ra t u re C o rre c t e d V o lt a g e
2 . 2 0 V / C e ll
2 . 2 4 V / C e ll
2 . 3 0 V / C e ll
2 . 3 5 V / C e ll
5 2 ℃ ( 1 2 6 F ) o r a b o v e
4 5 ℃ ( 1 1 3 F )
3 5 ℃ ( 9 5 F )
2 5 ℃ ( 7 7 F ) o r b e lo w
Figure 9. BTC-EQ MODE
7.4
Output Voltage FL Chage Mode Select (TEMP OFF)