9150-065-Y-12-20
26
Gate Frame
Gate Frame
Non-Secure Side
Outside Property
Secure Side
Inside Property
Filler Post or Barrier
Reversing Edge (Open Contact Sensor)
4.2 Entrapment Protection Device Locations
Typical Photo Sensor mounting height
and distance away from gate.
If the distance between the gate
and wall is greater than 2 1/4”.
Wall
UL sensor mounted on post.
UL sensor mounted on wall.
A filler post or barrier may need to be installed between the
gate and wall area to reduce the distance to 2 1/4”
or less
.
A reversing edge should be installed on the post or barrier
for safety (See page 2 for more information).
Photo Sensors (With Filler Post and Reverse Edge) Sample Setup
Closed Gate
Wall
Close Beam
UL 325 DIP-Switches
Photo sensors may be installed on either side of gate frame, as close as
practical to the gate but no further away than 5”.
No higher than
27.5” above grade.
21” is typical for
most installations.
Note: Additional
photo sensors can
be added above
the 27.5” height.
5”
or
Less
5”
or
Less
DIP-switches
1, 2 and 3 ON
1
ON
2
3
4
UL 325 Terminal
Connect
ONLY MONITORED
Devices
1 - OPEN Beam
2 - CLOSE Beam
3 - OPEN Edge
4 - CLOSE Edge
Only 1 monitored Device can be connected to each
input. An
OPTIONAL
Expansion Kit (sold separately)
will allow connection for additional devices.
1 - OPEN Beam (Switch 1)
2 - Ground (Common)
3 - CLOSE Beam (Switch 2)
4 - Ground (Common)
5 - 24 VAC 250 mA Max (Don’t exceed this)
6 - Ground (Common)
7 - OPEN Edge (Switch 3)
8 - Ground (Common)
9 - CLOSE Edge (Switch 4)
10 - Ground (Common)
Filler Post If necessary
Open Edge
Sensors Power Note:
Use separate power transformer to
power photo sensors that can be plugged into the built-in
convenience outlets located on the operator (See page 25).
See above and page 2 for filler post information.
Open Beam
Type of wiring to be used on ALL external devices:
A)
Type
CL2
,
CL2P
,
CL2R
, or
CL2X
.
B)
Other cable with
equivalent
or
better
electrical,
mechanical, and flammability ratings.
IMPORTANT:
Monitored Photo and
Edge sensors must be end-of-line
resistive types. See specific
manufacturer's wiring manual for
more information.
Note:
DIP-switches
MUST
be turned
ON
for each device
wired to terminal.
Entrapment Protection must be provided for the gate system where the risk of entrapment
or obstruction exists. The operator will NOT run without ONE or more monitored type B1 or
B2 external entrapment protection devices in EACH direction of gate travel (minimum of 2
external devices required).