9150-065-Y-12-20
27
Wireless Reverse Edge Sample Setup - Single Receiver
Closed Gate
Wall
Wireless Note:
Refer to the
instruction sheet that comes
with the receiver/transmitter for
more specific wiring, mounting
and “PROG” instructions.
Wireless Close Edge
Mount
MONITORED
transmitter on gate.
Filler Post (If necessary)
Wireless Edge
Transmitter
Coax Antenna Kit
P/N 1514-073
UL 325 Terminal
Connect
ONLY MONITORED
Devices
UL 325 DIP-Switches
DIP- switches
1, 3 and 4 ON
1
ON
2
3
4
1 - OPEN Beam
2 - CLOSE Beam
3 - OPEN Edge
4 - CLOSE Edge
Open Edge
1 - OPEN Beam (Switch 1)
2 - Ground (Common)
3 - CLOSE Beam (Switch 2)
4 - Ground (Common)
5 - 24 VAC 250 mA Max (Don’t exceed this)
6 - Ground (Common)
7 - OPEN Edge (Switch 3)
8 - Ground (Common)
9 - CLOSE Edge (Switch 4)
10 - Ground (Common)
Close
Edge
Open
Edge
Filler Post
MONITORED
Edge transmitter
mounted on gate.
Open
Beam
Only 1 monitored Device can be connected to each
input. An
OPTIONAL
Expansion Kit (sold separately)
will allow connection for additional devices.
Sensors Power Note:
Use separate power transformer to
power photo sensors that can be plugged into the built-in
convenience outlets located on the operator (See page 25).
See pages 2 and 26 for gate gap area and filler post information.
Open Beam
Receiver
MUST
monitor for the
presence of the transmitter.
Type of wiring to be used on ALL external devices:
A)
Type
CL2
,
CL2P
,
CL2R
, or
CL2X
.
B)
Other cable with
equivalent
or
better
electrical, mechanical, and flammability ratings.
Wireless CLOSE Edge (Relay 1)
ON DIP
1 2 3 4
+
CS1
GND ANT
PROG
C1 BS1
BS2 NO3 C3
ATEST
Com
CS2 C2
-
R3
R1
R2
MR
ATEST
CHECK
12/24 AC/DC
Set 4 to “OFF”
Power
Sold Separately
P/N - 8080-008 RF Monitored Gate Link Kit (RB-G-K10)
Miller Edge Sensing Edges - All models with a T2 (resistive) termination.
Gate Link
1
2
3
4
5
6
7
8
9
10
RB-G-K10
See manufacturer’s
manual to “PROG”
wireless edges.
IMPORTANT:
Monitored Photo and
Edge sensors must be end-of-line
resistive types. See specific
manufacturer's wiring manual for
more information.
Note:
DIP-switches
MUST
be turned
ON
for each device
wired to terminal.
Entrapment Protection must be
provided for the gate system
where the risk of entrapment or
obstruction exists. The operator
will NOT run without ONE or
more monitored type B1 or B2
external entrapment protection
devices in EACH direction of gate
travel (minimum of 2 external
devices required).