9150-065-Y-12-20
40
7.2 Troubleshooting
Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of
resistance is necessary to properly check the integrity of the ground loops. When a malfunction occurs, isolate the problem to
one of three areas:
1.
the operator,
2.
the loop system,
3.
the keying devices.
Use caution when checking high voltage
terminals, motor capacitor and the motor.
1.
Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is activated.
If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one
at a time until the LED goes OFF.
2.
Check any external entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to
stop or to hold open.
3.
A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is
present over the loop. Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction
persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to
your loop detector instruction sheet and to the DoorKing Loop and Loop Detector Information Manual.
4.
Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying
device fails to open the gate, press the Key Switch or momentarily jumper across terminals 4 and 18 on the operator circuit
board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.
5.
If a three-button control station (open-close-stop) is connected to this gate operator, check for proper wiring. Only a 4-wire
NC-Stop circuit type 3-button control station can be used with this gate operator. Make sure the control station jumpers are set
correctly or a malfunction will occur.
6.
Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will
cause the operator to malfunction. Refer to the wire size chart in section 2.1 on page 18.
Symptom
Possible Solution
(
s
)
•
Check that AC power to the operator is turned ON.
•
Transformer may be overheated. Turn power off and allow board to cool for several minutes then retest.
Check for low 115 VAC power and low voltage shorts.
•
Check for 115 VAC at high voltage terminal. If voltage measures 0, check the incoming power wires or replace
the circuit board.
•
Insure that a minimum of one (1) external entrapment protection device is connected in
EACH
direction of gate
travel (minimum of 2 external devices required) and the inputs are connected and enabled (UL 325
DIP-switches are turned ON).
•
Insure that the 3-button control station jumper are on pins 2 & 3 if not using a 4-wire 3-button control station.
•
If a photo-cell is used as a entrapment prevention device, check to be sure that the beam is not blocked.
•
Be sure that the chain is not too tight. A too tight chain may cause the operator to stall.
•
Bypass circuit board and
Check Motor:
Turn power switch OFF and remove the circuit board. Place a jumper wire from the 117 VAC SWITCHED
terminal to the BLUE wire on the 8 pin POWER connector on the control board.
CAUTION – HIGH VOLTAGE.
Turn the power switch on. The motor should run. Turn the power switch OFF and
remove the jumper.
With power still OFF, place a jumper wire from the 117 VAC SWITCHED terminal to the RED wire on the 8 pin
POWER connector on the control board.
CAUTION – HIGH VOLTAGE.
Turn the power switch on. The motor
should run in the opposite direction. Turn the power switch off and remove the jumper.
•
If the motor runs in both steps above, replace the control board. If the motor does not run, or runs in only one
direction, problem can be a bad motor, motor capacitor, motor resistors, wire connections from the control
board to the motor or a bad control board.
Operator will not
run. Power LED
is OFF.
Operator will not
run. Power LED
is ON.
Every time
the 9150 is powered up, the
First
open command will automatically run “
Multiple
gate cycles”
that will locate and remember the gate’s open and close positions (See page 23).