G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
19
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
STARTING
CAUTION
Use the EMERGENCY STOP button ONLY in the
event of an emergency.
NEVER use it for normal shut-down.
Verify the following:
1. All external electrical power loads are turned “OFF”.
2.
Main Breaker is “OFF”.
3. Battery Disconnected Switch is “ON”.
4. Reset (pull to unlatch) Emergency Stop Button.
5. Push the controller “START” Button.
DANGER
POWER is present upon cranking the engine.
CAUTION
Allow starter to cool for one minute between start
attempts.
If engine shuts down, diagnostic lamps will indicate
the problem. Correct the problem before continuing.
6. Allow the engine to warm-up for 3 to 5 minutes.
7. Check the CONTROL Panel for proper voltages. No
RED diagnostic lamps should be glowing.
8. With main breaker “ON” power is present and
available for use.
9. Close side doors for optimum cooling of the unit while
running.
STOPPING
1. Turn off all external electrical power loads.
2. Turn Main Breaker “OFF”.
3. Allow 5 minute cool down.
4. Push controller “STOP” Button.
5. Wait at least 15 seconds before restarting.
6. Fill fuel tank at end of working day to prevent
condensate.