G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
20
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
CONTROLLER
DESCRIPTION OF CONTROLS
CAUTION
The module may instruct an engine start event due to
external influences. Therefore, it is possible for the
engine to start at any time without warning. Prior to
performing any maintenance on the system, it is
recommended that steps are taken to remove the
battery and isolate supplies.
If engine shuts down, diagnostic lamps will indicate
the problem. Correct the problem before continuing.
Note: The following descriptions detail the
sequences followed by a module containing
the standard ‘factory configuration’. Always
refer to your configuration source for the
exact sequences and timers observed by any
particular module in the field.
Control of the module is via push buttons mounted
on the front of the module with Stop/Reset Mode
,
Manual Mode
, Test Mode
, Auto Mode
and Start
functions. For normal operation, these
are the only controls which need to be operated.
Details of their operation are provided later in this
document.
DSE7110 MKII
Menu
Navigation
Stop / Reset
Mode
Selected Mode
Indication LED
Generator
Breaker LED
Manual
Mode
Start
Auto
Mode
Alarm Mute
& Lamp Test
Generator
Available LED
Module
Display
Four user
configurable
status
indication
LEDs
Close
Generator
(Manual Mode
only)
Open
Generator
(Manual Mode
only)