G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
25
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
1. Warning Alarm Icons
Warnings are non-critical alarm conditions and do not affect the operation of the generator system. They serve to draw
the operator's attention to an undesirable condition.
By default, warning alarms are self-resetting when the fault condition is removed. However, enabling '
all warnings are
latched
' will cause warning alarms to latch until reset manually. This is enabled using the DSE Configuration Suite in
conjunction with a compatible PC.
ICON
FAULT
DESCRIPTION
Auxiliary Inputs
The module detects that an auxiliary input which has been user
configured to create a fault condition has become active.
Analogue Input
The module detects that an input configured to create a fault
condition has become active.
Fail To Stop
The module has detected a condition that indicates that the
engine is running when it has been instructed to stop.
NOTE:
'Fail to Stop'
could indicate a faulty oil pressure
sensor. If engine is at rest, check oil sensor wiring and
configuration.
Charge Failure
The auxiliary charge alternator voltage is low as measured from
the W /L terminal.
Low Fuel Level
The level detected by the fuel level sensor is below the
low fuel
level pre-set
pre-alarm setting.
High Fuel Level
The level detected by the fuel level sensor is above the
high fuel
level pre-set
pre-alarm setting.
Battery Under Voltage
The DC supply has fallen below or risen above the
low volts
pre-set
pre-alarm setting.
Battery Over Voltage
The DC supply has risen above the
high volts pre-set
pre-alarm
setting.
Generator Under Voltage
The
generator output voltage
has fallen below the
pre-set
pre-alarm setting after the Safety On timer has expired.
Generator Over Voltage
The
generator output voltage
has risen above the
pre-set
pre-alarm setting.
Generator Under
Frequency
The
generator output frequency
has fallen below the
pre-set
prealarm setting after the Safety On timer has expired.