3. Shutdown Alarm Icons
Shutdown alarms are latching and immediately stop the Generator. On initiation of the shutdown condition the module
de-energises all the '
Delayed Load Output
' and the '
Close Gen Output
' outputs to remove the load from the generator.
Once this has occurred, the module shuts the generator set down immediately to prevent further damage. The alarm
must be accepted and cleared, and the fault removed to reset the module.
Note: The alarm condition must be rectified before a reset will take place. If the alarm condition remains, it is
not possible to reset the unit (The exception to this is the Low Oil Pressure alarm and similar 'active from
safety on' alarms, as the oil pressure is low with the engine at rest).
Shutdowns are latching alarms and to remove the fault, press the
Stop/Reset Mode
button on the
module.
ICON
FAULT
DESCRIPTION
Auxiliary Inputs
The module detects that an auxiliary input which has been
user configured to create a fault condition has become
active.
Analogue Input
The module detects that an input configured to create a
fault condition has become active.
Fail To Start
The engine has failed to start after the configured number
of start attempts.
Low Oil Pressure
The module detects that the engine oil pressure has fallen
below the low oil pressure pre-alarm setting level after the
Safety On timer has expired.
Engine High Temperature
The module detects that the engine coolant temperature
has exceeded the high engine temperature pre-alarm
setting level after the Safety On timer has expired.
Under Speed
The engine speed has fallen below the under speed
pre-alarm setting.
Over Speed
The engine speed has risen above the over speed
pre-alarm setting.
Charge Failure
The auxiliary charge alternator voltage is low as measured
from the W/L terminal.
Low Fuel Level
The level detected by the fuel level sensor is below the low
fuel level pre-set alarm setting.
High Fuel Level
The level detected by the fuel level sensor is above the
high fuel level pre-set alarm setting.