Generator Under Voltage
The generator output voltage has fallen below the pre-set
alarm setting. after the Safety On timer has expired.
Generator Over Voltage
The generator output voltage has risen above the pre-set
alarm setting.
Generator Under Frequency
The generator output frequency has fallen below the
pre-set alarm setting after the Safety On timer has expired.
Generator Over Frequency
The generator output frequency has risen above the
pre-set alarm setting.
Delayed Over Current
The measured current has risen above the configured trip
level for a configured duration.
kW Overload
The measured kW has risen above the configured trip level
for a configured duration.
CAN ECU Fault
The engine ECU has detected an alarm - CHECK ENGINE
LIGHT Contact Engine Manufacturer for support.
CAN Data Fail
The module is configured for CAN operation and does not
detect data on the engine Can data link.
Emergency Stop
The emergency stop button has been depressed. This
fail-safe (normally closed to emergency stop) input and
immediately stops the set should the signal be removed.
Oil Sender Open Circuit
The oil pressure sensor has been detected as being open
circuit.
Coolant Temperature Sender
Open Circuit
The coolant temperature sensor has been detected as
being open circuit.
Oil Filter Maintenance Alarm
Maintenance due for oil filter.
Air Filter Maintenance Alarm
Maintenance due for air filter.
Fuel Filter Maintenance Alarm
Maintenance due for fuel filter.