G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
38
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
Stop Mode
Manual Mode
Test Mode
Auto Mode
•
Scheduled runs do not occur when the
module is in
Stop/Reset Mode
.
•
Scheduled runs do not occur when the
module is in
Manual Mode
waiting for a
start request.
•
Activation of a Scheduled Run 'On load'
when the module is operating OFF LOAD
in
Manual Mode
will force the set to run
ON LOAD.
•
Scheduled runs do not occur when the
module is in
Test Mode
waiting for a start
request.
•
Scheduled runs operate ONLY if the
module is in
Auto Mode
with no Shutdown
or Electrical Trip alarm present.
•
If the module is in
Stop/Reset Mode
or
Manual Mode
when a scheduled run
begins, the engine is not started.
However, if the module is moved into
Auto
Mode
during a scheduled run, the engine
will be called to start.
•
Depending upon configuration by the
system designer, an external input can be
used to inhibit a scheduled run.
•
If the engine is running OFF LOAD in
Auto
Mode
and a scheduled run configured to
'On Load' begins, the set is placed ON
LOAD for the duration of the Schedule.