G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
39
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
FAULT FINDING
STARTING
SYMPTOM
POSSIBLE REMEDY
Unit is inoperative
Read/Write configuration does
not operate
Check the battery and wiring to the unit.
Check the DC supply.
Check the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9 Volts.
Check the operating temperature is not above 70°C.
Check the DC fuse.
Fail to Start is activated after
pre-set number of attempts to
start.
Check wiring of fuel solenoid.
Check fuel.
Check battery supply.
Check battery supply is present on the Fuel output of the module.
Check the speed-sensing signal is present on the module's inputs.
Refer to engine manual.
Continuous starting of generator
when in the
Auto Mode
.
Check that there is no signal present on the 'Remote Start' input.
Check configured polarity is correct.
Check the mains supply is available and within configured limits.
Generator fails to start on receipt
of Remote Start signal.
Check Start Delay timer has timed out.
Check signal is on 'Remote Start' input.
Confirm correct configuration of input is configured to be used as 'Remote Start'.
Check that the oil pressure switch or sensor is indicating low oil pressure to the
controller.
Depending upon configuration, then set will not start if oil pressure is not low.
Pre-heat inoperative
Check wiring to engine heater plugs.
Check battery supply.
Check battery supply is present on the Pre-heat output of module.
Check pre-heat configuration is correct.
Starter motor inoperative
Check wiring to starter solenoid.
Check battery supply.
Check battery supply is present on the Starter output of module.
Ensure oil pressure switch or sensor is indicating the 'low oil pressure' state to
the controller.