OPERATION
Note: The following descriptions detail the
sequences followed by a module containing
the standard 'factory configuration'. Always
refer to your configuration source for the
exact sequences and timers observed by any
particular module in the field.
QUICKSTART GUIDE
This section provides a quick start guide to the module's
operation.
Starting the engine
Stopping the engine
STOP/RESET MODE
Note: If a digital input configured to
panel lock
is
active, changing module modes will not be
possible. Viewing the instruments and event
logs is NOT affected by
panel lock
.
If the engine does not stop when requested, the FAIL TO
STOP alarm is activated (subject to the setting of the
Fail
to Stop timer
). To detect the engine at rest the following
must occur:
•
Engine speed is zero as detected by the CANbus
ECU.
•
Generator AC Voltage and Frequency must be zero.
•
Engine Charge Alternator Voltage must be zero.
•
Oil pressure sensor must indicate low oil pressure.
When the engine has stopped, it is possible to send
configuration files to the module from DSE Configuration
Suite PC software and to enter the Front Panel Editor to
change parameters.
Power Save Mode in the DSE Configuration Suite
Software.
Press the
Manual Mode
button . .
. . followed by
the Start button
Select Stop/Reset
mode. The
generator is
stopped.
Stop/Reset
Mode is activated by pressing the
Stop/Reset
Mode button. The
Stop/Reset
Mode icon is displayed to indicate
Stop/Reset
Mode operations.
In
Stop/Reset
Mode, the module removes the
generator from load (if necessary) before
stopping the engine if it is already running.
Any latched alarms that have been
cleared are reset when
Stop/Reset
Mode
is entered.
The engine is not started when in
Stop/
Reset
Mode. If remote start signals are
given, the input is ignored until
Auto
Mode
is entered.
When left in
Stop/Reset Mode
with no
presses of the fascia buttons and
configured for 'Power Save Mode', the
module enters Power Save Mode. To
'wake' the module, press any fascia
control buttons.