G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ
OPERATION & MAINTENANCE MANUAL
37
G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz
MAINTENANCE ALARM
Depending upon module configuration one or more levels
of engine maintenance alarm may occur based upon a
configured schedule.
Example 1
Screen capture from DSE Configuration Suite Software
showing the configuration of the Maintenance Alarm for
Oil, Air and Fuel.
When activated, the maintenance alarm can be either a
Warning
(set continues to run) or
Shutdown
(running
the set is not possible).
Resetting the
Maintenance Alarm
is normally actioned by
the site service engineer after performing the required
maintenance. The method of reset is either by:
Example 2
Screen capture from DSE Configuration Suite Software
showing the configuration of a digital input for
Maintenance Reset Alarm Air.
Example 3
Screen capture from DSE Configuration Suite Software
showing the Maintenance Alarm Reset 'button' in the
DSE Configuration Suite SCADA I MAINTENANCE
section.
SCHEDULER
The controller contains an inbuilt exercise run scheduler,
capable of automatically starting and stopping the set. Up
to 8 scheduled start/stop sequences can be configured to
repeat on a 7-day or 28-day cycle. Scheduled runs may
be on load or off load depending upon module
configuration.
Example
Screen capture from DSE Configuration Suite Software
showing the configuration of the Exercise Scheduler. In
this example the set will start at 09:00 on Monday and
run for 5 hours, then start at 13:30 on Tuesday and run
for 30 minutes.
•
Activating an input that has been
configured to
Maintenance Reset Alarm
x,
where x is the type of maintenance alarm
(Air, Fuel or Oil).
•
Pressing the maintenance reset button in
the
DSE
Configuration
Suite,
Maintenance section.
•
Pressing and holding the
Stop/Reset
Mode
button for 10 seconds on the
desired Maintenance Alarm status page.
This can be protected by a PIN number.