CLEANING THE COOLING CIRCUIT
If the internal coolant circuit is contaminated by corrosion
or foreign substances, the cooling effect is reduced. The
resistance in the coolant circuit may damage the
mechanical seal of the coolant pump.
The reduced performance in the cooling circuit may be
caused by use of incorrect type or quantity of antifreeze
or corrosion inhibitor, or by use of coolant without such
ingredients. If the coolant pump leaks or the coolant is
severely contaminated within the first 6 months of
operation (e.g., the coolant color becomes discolored -
brown, grey or black depending on the degree of
contamination), clean the cooling system in the following
way before removing the cooling pump.
1. Drain the coolant.
2. To clean the cooling circuit swiftly, remove the
thermostat.
3. Mix water and 1.5% of cleaning solution and fill the
cooling circuit with this liquid.
4. Load the engine. When the coolant temperature
reaches 60°C, run the engine for approximately 15
minutes.
5. Drain the cleansing solution.
6. Repeat step 3 and 4 above.
7. Fill the cooling circuit with hot water.
8. While running the engine at idle speed for 30 minutes,
check if there is any leakage in the drain plug and
coolant line. If the coolant is insufficient, replenish it.
CAUTION
Clean the cooling circuit regularly with cleansing
solution.