DIAGNOSTICS / AUTO SHUTDOWN (ANALOG CONTROLLER)
Figure 23
The operating controls and instruments are arranged on
the control panel as shown. A description of each panel
device is as follows:
1.
High Engine Temperature -
Indicates engine
shutdown due to high coolant temperature or low
coolant level.
2.
Low Engine Oil Pressure -
Indicates engine
shutdown due to low engine oil pressure.
3.
Low Fuel Level -
Indicates engine shutdown due to
low fuel level.
4.
High Containment Level -
Indicates high level of
fluids in the containment base.
5.
Over Crank -
Indicates engine did not start after 3
cranks.
6.
Battery Not Charging -
Indicates battery voltage is
low or not being charged.
7.
Engine Speed -
Indicates engine overspeed.
8.
Engine Operating -
Indicates engine is cranking or
operating.
9.
Preheat -
Indicates preheating is on.
10.
Engine Communication -
Indicates the controller
has communication with the engine ECU.
11.
Engine Fault -
Indicates that engine service may be
required.
12.
Engine Start Switch.
13.
Engine Stop / Reset Switch -
Stops engine and
resets diagnostics. Also, awakens controller from
sleep mode. Wait 15 seconds for reset to complete
before attempting start.
14.
Autostart Mode Switch -
Puts engine in Autostart
Mode.
15.
Autostart Mode -
Indicates genset is in Autostart
Mode. Note: the controller will enter low power sleep
mode after a short time and all other LED’s will go off.
16.
Emergency Stop Switch -
Disables running,
cranking, and trips main breaker. (Not shown.)
17.
Alarm Horn -
Sounds prior to a start when in Auto
Start Mode. (Not shown.)
Summary of Contents for G20 SIIIA
Page 2: ......
Page 4: ...4 G20 30 40 SIIIA Operation Maintenance Manual ...
Page 10: ...10 G20 30 40 SIIIA Operation Maintenance Manual ...
Page 15: ...15 G20 30 40 SIIIA Operation Maintenance Manual WARNING Flammable liquid ...
Page 20: ...20 G20 30 40 SIIIA Operation Maintenance Manual ...
Page 121: ......