background image

DORMA

ED 200 ESR

WN 056461  45532

 06/12

Installation of control unit

Control unit A = Standard unit

Control unit B = Enhanced unit
Screw in screw and washer assembly in cylinder

unit. Put all cables to the front. Push the PCB

holder and the control unit below the screw heads

and fix it.
Fix the connectors. Please refer also to connection

diagrams/wiring diagrams for the following points.

Connect the cable of the program switch to the

control unit.

Connect additional components to the control unit

when available. Please consider connection

diagrams/wiring diagrams for this.
Adjust door opening angle: Move door leaf to

required open position and adjust black cam using

pin supplied until the cam activates the

microswitch. Fix cam in this position.

Switch must be activated at an angle less

than 115° (max. door opening angle) to
allow motor pump to switch off.

When using control unit „B“ adjust mode switch:

A = single leaf operation

B = double leaf operation

C = application with motor lock
Set both mains ON/OFF switch 1 and program

switch 2 to "OFF".

Connect to mains.

Unlatch Emergency pushbutton ( usually next to

door).

Set mains ON/OFF switch 1 to "ON".

Set programme switch 2 to "AUTOMATIC".
Activate operator by means of eg. radar or

pushbutton, and check performance. Adjust

settings as required.
Opening speed adjustable at valve 1 in the range 0

o

 - 75

o

.

Backcheck action adjustable at valve 2 in the

range 75

0

 - 115

0

.

Adjust hold-open time by potentiometer in the

range from 0 - 30 secs.

Note:

     For the door to reach the open position, the

hold-open time must be adjusted to a larger value

that the total time set at valves 1 and 2. The hold-

open time starts with the activation signal.

   0

7

23

22

19

20

21

Optional IRS safety sensor on hinge-side.

If necessary use white cam to adjust the blanked

range of the IRS sensor (i.e. area for which sensor is

disabled). Turn the cam with the pin supplied until

the microswitch is activated. Ensure that the position

of the black cam remains unchanged.

Note:

 As the door opens to this point, the hinge-side

IRS sensor ceases to operate so that the door is not

tripped by obstacles in the blanked range.

Ensure that the white cam, once adjusted,
does not also activate the limit switch in the
“Door Closed” position.

Sensors in accordance with the relevant installation

instructions.

Functional tests

Possible program switch settings:
Programme switch integrated in ED 200:
AUTOMATIC - OFF - PERMANENT OPEN
External programme switch:
OFF - EXIT ONLY - PERMANENT OPEN - AUTOMATIC

(only possible with control unit B).
Check internal activator.

Door opens after signal emission in “AUTOMATIC”

and “EXIT ONLY” modes, on expiry of hold-open

time.

Check external activator.

Door opens after signal emission in “Automatic” and

“Exit only modes” and closes on expiry of hold-open

time.

Option: “Push and Go“

Once door has been slightly moved from its closed

position, operator moves leaf to complete open

position

and closes door after preset hold-open time.

Option: ”Night-/Bank Function” activator

(only possible with control unit B).

Door unlocks and opens on signal emission with

program switch set to “OFF”. After approx. 5

seconds, door closes again automatically.

Option: IRS safety sensor

Hinge-side:

If the IRS detects an obstacle (person) in its

detection range

- the door stops moving during the opening cycle

- the door stays closed if already in closed

position.

Once the detection range is free, the operator is re-

enabled and continues operation in the preset mode.
Opposite hinge side:

If the IRS detects an obstacle (person) in its

detection range

- the door reverses during closing cycle

- the door stays open if already in open position

Once the detection range is free, the operator is

re-enabled and continues operation in the preset

mode. The IRS on the opposite hinge side is switched

off automatically by the control unit after 5 sec. and

reactivated only when door starts moving again.

26

25

24

27

Summary of Contents for ED 200 ESR

Page 1: ...hutzmaßnahme ausreichend Die Haupt und Nebenschließkanten müssen zusätzlich abgesichert werden Schutzflügel Sensoren Zur Einhaltung der Vorschrift müssen die statische Kraftbegrenzung die Schleichfahrtstrecken und die Geschwindigkeiten in Abhängigkeit zum Türflügel gewicht eingestellt werden Die dynamischen Kräfte müssen vor Ort mit einem Kraftmessgerät geprüft und die Einstellungen ggf geändert w...

Page 2: ...l schieben Endstücken auf Gleitschiene stecken Ventile 3 und 4 öffnen Gleitschiene am Türblatt befestigen 11c 12c 11b 8a 12a 8c 9c 10c 11a 9a 8b 9b 10b 13 16 17 15 14 18 10a 12b Montage Gleitschiene Bandseite Markierung auf Hebelauge L Hebelauge für DIN links Türen R Hebelauge für DIN rechts Türen Hebelauge in Hebel einsetzen Stellung des Vierkants zum Hebel beachten Hebelauge mit einem Hammer und...

Page 3: ...ereich wieder frei nimmt der Antrieb seinen normalen Betrieb wieder auf Bandgegenseite Befindet sich ein Hindernis im Erfassungsbereich der IRS Sicherheitsleiste reversiert die Tür bei der Schließfahrt bleibt die Tür in geöffneter Position stehen Ist der Überwachungsbereich wieder frei nimmt der Antrieb seinen normalen Betrieb wieder auf Steuerung B schaltet die Sensorleiste nach 5 Sek ab Sie ist ...

Page 4: ...it Steuerung B Die Tür ist im geschlossenen Zustand verriegelt Bei jeder Aktivierung eines Öffnungsimpulsgebers wird das Motorschloss entriegelt und die Tür öffnet Restmontage Schutzleiterkabel aufstecken Abdeckhaube aufsetzen und anschrauben Firmen Logo anbringen Bei der Montage ist auf die Absicherung der Nebenschließkante zu achten Einweisung Nach erfolgter Einstellung Inbetriebnahme der Türanl...

Page 5: ... the secondary closing edges have to be protected by further safety equipment Safety screens sensors In order to comply with this standard the static force limitation the driving phase for the low creep speed cycles and the speed have to be adjusted according to the door leaf weight The dynamic forces have to be checked on site with the aid of a dynamometer or similar and the respective settings h...

Page 6: ...slide channel Dimensional drawing Installation on pull side hinge side with slide channel Standard setting on delivery is for right handed DIN R ISO 5 CW closing doors To fit the operator to a left handed door the microswitch and the cam must be refitted on the other end of the axle Pull out the plastic nut and unscrew the end cap In the case the complete system can be installed direct attach it t...

Page 7: ...urn the cam with the pin supplied until the microswitch is activated Ensure that the position of the black cam remains unchanged Note As the door opens to this point the hinge side IRS sensor ceases to operate so that the door is not tripped by obstacles in the blanked range Ensure that the white cam once adjusted does not also activate the limit switch in the Door Closed position Sensors in accor...

Page 8: ...n the operator is activated the motor lock unlocks and the operator opens the door Completion of installation Connect earthing cable Install cover and fix with two screws Fix DORMA and ED 200 labels Pay attention to protect the secondary closing edges during installation Briefing After commissioning and adjustment of the operator and accessories the operating instructions must be handed to the own...

Reviews: