54
ED50/ED100/ED250
09-2021
DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Opening speed, automatic mode
5
ED50
8- 27*
°/s
25
ED50: low energy only.
*
ED50 adjustable opening speed range.
ED100/ED250
Full adjustable range of opening speeds available only when configured for full energy
(Parameter F2).
**Maximum opening speed reduced to 27°/s in low energy mode.
1. After adjustment, internal monitoring system checks if parameter setting is
admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
2. After adjustment, Internal monitoring system checks if parameter setting is
admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standards
A156.10 (full energy) or A156.19 (low energy) standards. Reference Chapter 19.
ED100
2- 50**
°/s
ED250
2 - 60**
°/s
Closing speed, automatic mode
5
ED50
8- 27*
°/s
25
ED50: low energy only.
*
ED50 adjustable closing speed range.
ED100/ED250
Full adjustable range of closing speeds available only when configured for full energy
(Parameter F2).
**Maximum closing speed reduced to 27°/s in low energy mode.
1. After adjustment, internal monitoring system checks if parameter setting is
admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
2. After adjustment, Internal monitoring system checks if parameter setting is
admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standards
A156.10 (full energy) or A156.19 (low energy) standards. Reference Chapter 19.
ED100
2- 50**
°/s
ED250
2 - 60**
°/s
Hold open time, automatic mode
• Hold open time starts once all internal, external, safety and push and go inputs have
been opened or dropped, and door is in an open position; Hold open time can be
re-triggered.
• Hold open time values from 0 to 30 are set in increments of 1 second.
• *Parameter
F2
, when set to full energy, extends maximum hold open time to 180
seconds.
• Hold open time values greater than 30 seconds are set in increments of 5 seconds.
7
0 - 30
s
5
0 - 180*
s
Appendix A - Driving parameters
A.1 Driving parameters – detail
A.1.1 Driving parameters detail.