61
ED50/ED100/ED250
09-2021
DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Power assist function
• Force setting for Power assist function.
• Power assist function only available with
hd
parameter = 1, manual mode.
• "0"; power assist function OFF. Power assist function enabled for available values
greater than 0.
• Power assist function enabled when power assist activation angle
hA
reached.
• The greater the value of
hF
, the easier the door can be manually opened from power
assist activation angle
hA
.
• If power assist set too high, door can open automatically.
• Power assist function is not available
• If operator is switched off., A smoke detector or emergency button has been
triggered.
36
0 - 10
0
Additional Power assist function support
from 0
0
• Setting for additional power assist function support from 00.
• The greater the value of
hS
, the easier the door can be manually opened from 00.
37
0 - 99
0
hS
A1.1.1 Upgrade card units codes
0 - 3
0
0
Upgrade card not installed, function not available.
1
Upgrade card installed, function not activated.
2
Upgrade card installed, function activated.
3
Upgrade card has been removed, function no longer available.
Upgrade card fire protection
1. Activate function by installing upgrade card, parameter value will automatically
change to 2 (upgrade card function installed, fire protection function activated).
• Following activation, drive may be used as a electrically controlled hold-open
system according to EN 14637, Building hardware-Electrically controlled hold-
open systems for fire/smoke door assemblies, or similar standards.
• Full energy function (
F2
) is automatically activated (ED100/ED250).
• Plug for terminal board X9 socket included with upgrade card.
38
Available
upgrade card
codes
(Para. A1.1.1)
0, 2, 3
0
Full energy– upgrade card not required to
enable function.
ED50: low energy only
(ANSI/BHMA A156.19)
.
• F2=0, no parameter adjustment.
39
Available
upgrade card
codes
(Para. A1.1.1)
0, 2, 3
0
ED100/ED250
• F2 default is 0, low energy (ANSI/BHMA A156.19).
1. To activate
Full energy function
(ANSI/BHMA A156.10) change parameter
F2
to 2.
• The full setting range of parameters
So, Sc, Fo
and
Fc
will be available after the
activation.
• SL
(Factory setting level) of 2 will reset
F2
to 0.
Not used.
40
0
Not used.
41
0
Not used.
42
0
A.1.1 Driving parameters detail.