63
ED50/ED100/ED250
09-2021
DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Release of hold-open system
50
0 - 1
1
1
1. Upgrade care Fire Protection installed.
2. Set parameter
FC
to 1. Users may release hold-open by manually moving door
in closed direction.
• A manual release button is not required.
0
• Hold-open release by manually moving door in closed direction is deactivated.
• A manual release button is required.
Castor angle for double doors
Primary door with astragal, angle active door must open before secondary door opens.
51
0 - 30
°
30
Hinge clearance
• Clearance between hinges is critical for the calculated door angle.
• HS
parameter may only have a small effect but the hinge clearance can be adjusted
in extreme cases to improve accuracy.
• Factory setting is 3 * 10, 30 mm, 1 3/16".
• With CPD doors, setting must be changed to a negative value. A learning cycle is
then required as system creates an angle table as a function of the set parameters.
52
±
5
*10
mm
3
*10
±
3/16
*10
inches
Overhead concealed mode (OHC): Activation
of permanent open via night-bank input
53
0 - 1
0
0
Function disabled.
1
If night-bank signal is longer than 3 seconds, operator changes to permanent open
mode.
Overhead concealed mode (OHC):
Adjustable behavior after blockage / hold
open
54
0 - 1
0
0
Standard behavior (3 x restart).
1
Manual mode after blockage.
Reversing after trigger of approach side
safety sensor / opposite hinge side in
operating mode hd=1
55
0 - 1
0
0
Standard behavior, stop.
1
Reversing
A.1.1 Driving parameters detail.