dormakaba 8600 EMR Installation Instructions
08281010
03-2020
8600 EMR
12
Wiring: SD-2 detector
Wiring: Solenoid attachment
4.6 SD-2 detector to main electromagnet` connection
Fig.14
SD-2
Strip approximately 1/4” of plastic insulation from the end of the two electromagnet wires supplied. Connect
one end each of the electromagnet wires to terminals 6 & 9 of the SD-2 detector as shown.
13
12
1
8
2
9
10
3
4
5
6
7
15
14
11
Main hold open
electromagnet
4.7 SD-2 detector to auxiliary solenoid connection
Fig.15
Main hold
open
electromagnet
Auxiliary hold open
electromagnet
13
12
1
8
2
9
10
3
4
5
6
7
15
14
11
NOTE: Make this connection the same time as the main hold open
solenoid connection. Strip approximately 1/4” of plastic insulation
from the ends of the wires. Connect auxiliary hold open solenoid wires
to 9 & 6 of SD-2 detector.
4.8 Solenoid attachment to UL/ULC listed alarm control panel
Fig.16
UL/ULC listed
alarm control
panel
Hold open
electromagnet
Some applications may require input power to the hold open electromagnet to be supplied through a UL/ULC
listed alarm control panel so the hold open electromagnet functions separately from the internal detector
module. This application requires the alarm contacts of the SD-2 detector and any remote detectors to be
connected to the alarm contacts of the control panel. An alarm indication to the panel results in the loss of
power to the hold open electromagnets in the related zone, which allows the doors to close. Wire main
electromagnet to alarm control panel as illustrated.
P
ow
er
In
24Volt Only