103
ED50
08-2018
DL4614-140
dormakaba ED50 OHC Installation Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Push & Go
22
0 - 1
0
0
Off
1
1. Parameter is activated.
2. Automatic opening of door is started when door is manually moved 4° out of the
closed position.
3. Door close mode parameter
hd
must be set to "0" (manual) to enable this
function.
Program switch type
23
0 - 4
0
0
Internal, operator mounted program switches are active.
1
External mechanical program switch with contacts is connected to operator
terminal board.
Internal program switch connector must be removed.
2
External DCW
®
electronic program switch (EPS) is connected to operator terminal
board.
Internal program switch connector must be removed.
3
Program switch control by TMS Soft control software.
4
1. DCW
®
electronic program switch (EPS) is installed, and operator is also
connected by the building management system to TMS Soft control software.
2. When PS is set to 4, the program switch functions can be changed from DCW®
(EPS) to TMS Soft (v1.9).
DCW Electronic program switch (EPS)
behavior following power reset
24
0 - 1
0
0
1. In event of power failure, or if operator is deliberately switched off, EPS will
automatically switch to last known position when power returns.
2. Important:
The time at which power returns might not be during business hours
and may affect insurance-compliant door locking requirements.
1
1. In event of power failure, or if operator is deliberately switched off, EPS will
automatically switched to OFF position when power returns.
2. This function should be used if insurance compliant locking if required.
Internal program switches, switch on delay
25
0 - 1
0
0
Operator will perform function of new switch setting as soon as internal program
switch is moved.
1
1. Operator will perform function of new switch setting after a delay of 10 seconds
from when internal program switch is moved.
2. This function is useful if user has to pass through door and its connected
detectors and sensors after program switch is set to new function.
Unlocking during business hours
26
0 - 1
0
0
Door is always locked when it reaches closed position.
1
1. In automatic mode, door will not lock when it reaches closed position. This
achieves faster door opening when system is equipped with motor driven locks.
2. If an electric strike opener is used, it must be suitable for 100% continuous duty
factor to avoid possibility of damage.