115
ED50
08-2018
DL4614-140
dormakaba ED50 OHC Installation Instructions
Appendix C
#
Parameter and
default
Description / Selections
1
Installation
*
Pull arm
Push arm
Gleit BGS (Track w push arm)
cm
Inches
2
Reveal depth
0
-
ED50
-3 ... 50
-1 3/16 ...
19 11/16
3
Door width
(steps of 4")
100
ED50
70 ... 160
28 ... 63
4
Door type
*
single
*
1. leaf
2. leaf
Master
Slave
11
Sensor test
0
0
off
1
Pull side high active
2
Push side high active
3
Both sides high active
4
Pull side low active
5
Push side low active
6
Both sides low active
7
Bodyguard
#
Parameter and
default
Description / Selections
12
Start safety
push side
*
Off
*
Signal ignored once
door closed
On
Sensor can trigger
pulse with door closed
14
Lock delay
3
Delayed opening time
for locking mechanism
(0 ... 3)
*100
msec
15
Unlock force
0
Preload prior to
unlocking
0 ... 9
12
Test PR
module
*
0
*
Test off
1
*
Test once every 24 hrs.
23
Program
switch
*
Internal
*
External
DCW
24
PGS power
up (DCW)
*
Last
*
Off
25
PGS delay
*
Off
*
On
26
Daytime
unlock
*
Off
*
On
Locking device remains
permanently unlocked
while door is in closed
position.
27
Door status
(Status relay
function, X7
terminals)
*
Off
Relay off
Open
*
Door reaches closed
position
Close
Door reaches open
position
Error
Any error message
Door closed and locked
Information or error
codes displayed
Door opened further
than opening angle
C.2 Configuration parameters
"#" refers to reference numbers in Parameter list
, Appendix
C.2.1 Configuration parameters
NOTICE
Parameters and detail may change depending
on firmware version.