dormakaba ED900 Installation Instructions – Double egress door
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Not used.
39
Upgrade card professional, impulse relay
Not available
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F3
to 2.
3. Door can be controlled with a pushbutton connected to Night-bank input without a
door hold open time:
• Door opens with first pulse and remains open. The hold open time is not limited.
• Door closes only with second pulse of pushbutton.
4. Pushbutton in 3. must be connected to terminal board Night-bank input:
• X1, 3 and 35 (dry)
• X10, 57 and 57a (wet)
5. Standard hold-open time
dd
is available when door is opened using other internal and
external detectors.
40
0, 1,
2, 3
0
Upgrade card professional, extended
hold-open time
Not available
1. Once upgrade card installed, parameter value will automatically change to 2.
2. Setting range of
dd
, hold -open time is extended from 0 - 30 s to 0 - 180 s.
41
0, 2, 3
0
Upgrade card professional, nurse - bed
function (double doors only)
Not available
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F5
to 2.
3. For double doors, this function enables:
• Separate door opening (only active door, nurse)
• Both doors open (active, inactive doors, bed)
4. The activator connected to the external detector (terminal board X4, 41 and 3)
controls the active door (nurse function). Only the active door will open.
5. The activator connected to the internal detector (terminal board X4, 42 and 1) controls
the both active and inactive doors (bed function), both doors will open.
6. If Push & Go function
PG
is activated, only the active door will open in the event of a
manual opening.
7. Night-bank inputs will only cause the active door to open.
8. Exit only program switch function is not available with
F5
activated.
42
0, 1,
2, 3
0
Upgrade card barrier free toilet
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F7
to 2.
3. Operator power reset is required; turn power switch off, wait 10 s and turn power back
on.
4. Upgrade card assigns inputs and outputs of the control unit with functions which are
required for this application.
43
0, 1,
2, 3
0
Upgrade card DCW
®
Not used.
44
0, 2, 3
0
COM 1 configuration interface
45
0 - 1
0
0
Interface programmed for communication with dormakaba handheld.
1
Interface programmed for use with Dorma USA, Inc. TMS Soft control software.
A.1.1 Driving parameters detail.