17
Wiring EML
Fig. 14
6.1.1
Remove wiring cavity cover.
6.1.2
Route the power supply connecting wire
through the frame/header tube/shim (as
necessary) and into the wire access hole.
Total one way
length of wire run (ft.)
Load current
1/4A
1/2A
3/4A
1A
1-1/4A
1-1/2A
2A
3A
100
20
18
16
16
14
14
12
10
150
20
16
14
14
12
12
10
--
200
18
16
14
12
12
10
10
--
250
18
14
12
12
10
10
--
--
300
16
14
12
10
10
--
--
--
400
16
12
10
10
--
--
--
--
500
14
12
10
--
--
--
--
--
750
12
--
--
--
--
--
--
--
1000
12
--
--
--
--
--
--
--
NOTE: Power supply should be of sufficient gauge for
the lock being installed and the distance being run. See
Table 1 and 2 for reference.
Table 1
Wire gauge selections - load current at 24V
Total one way
length of wire run (ft.)
Load current
1/4A
1/2A
3/4A
1A
1-1/4A
1-1/2A
100
18
16
14
12
12
10
150
16
14
12
10
10
--
200
16
12
10
10
--
--
250
14
12
10
--
--
--
300
14
10
--
--
--
--
400
12
10
--
--
--
--
500
12
--
--
--
--
--
750
10
--
--
--
--
--
Table 2
Wire gauge selections - load current at 12V
Header
tube
NOTE: Header tube
hidden for easier
viewing.
Shim
Shim
Mag lock
body
Mag lock
body
Wiring
cavity
cover
Power
supply
NOTE: Shim
and lock body
exploded for
easier
viewing.
Wiring
cavity
Wire access
hole
Power
supply
These recommended wire gauge selection tables are based on the 2008 National Electrical Code (2008 NEC),
assume 140°F (60°C) rated wire, include a 25% safety factor, and define the amperage ratings at the listed
distances that result in 5% voltage drop due to wire resistance. Five percent is normally acceptable in low voltage
systems.
6 Wiring the EML
6.1
Wiring mag lock body through header (for EML310/320 and 371/372)
Wire access