7  Status display

The door unit’s status display is indicated via the 
illuminated ring on the emergency button. The LED 
segments light up or blink in color depending on the 
door status. In the event of an alarm, an signal sounds 
as well.

 

WARNING

The service technician must be called 
immediately in the event of a permanent 
alarm or an unidentifiable display on the 
illuminated ring.

Table of displays on the emergency button’s 
illuminated ring

LED display

Door status

Recommended procedure

1. LED display in normal operation

The electric  
door locking device is 
activated.

 

 

A          B          C

The electric door locking 
device is  
A. briefly unlocked
B. unlocked long-term* or
C. permanently unlocked

2. LED display in case of alarm

 

“Door open” alarm
(one yellow LED per locking 
device, here: 4 connected 
locks)

Turn off the alarm signal (see Ch. 4.6)

Emergency button pressed

Turn off the alarm signal (see Ch. 4.6)

Alarm system triggered

After resetting the fire detector or smoke 
switch, this alarm trigger is automatically 
reset.

 or 

 

Tamper alarm
red-yellow = locked door
green-yellow = unlocked door

Check all the connected devices’ housings 
for correct screw connection and seal them 
correctly

 

if necessary. Turn off the alarm 

signal (see Ch. 4.6).  If the alarm continues, 
call the service technician.

3. LED display in case of malfunction or maintenance

(no display)

Power supply is missing 
or emergency button is 
defective

Turn on the power.

  

If the LED display does not change, call the 
service technician. 

 or 

Maintenance required 
•  red-yellow = locked door
•  green-yellow = unlocked 

door

Inform the facility operator and/or call the 
service technician.

*Long-term unlocking from Standard license

Tr

anslation o

the original documen

t, subjec

to change 

witho

ut no

tic

e

Summary of Contents for SafeRoute-System Mini

Page 1: ...Obligations of the user 2 3 Product description 2 4 Operation 3 4 1 Deactivate the electric locking device in an emergency 3 4 2 Briefly unlock the electric locking device 3 4 3 Unlock the electric locking device long term from Standard license 3 4 4 Permanently unlock the electric locking device 3 4 5 Reactivate the electric locking device after unlocking 3 4 6 Turn off the alarm signal 3 5 Maint...

Page 2: ...ins the operation of the SafeRoute escape route security system 1 2 Target group This manual is intended for the facility operator and user of the emergency exit door 1 3 Documents storage This manual is to be kept for the entire service life 1 4 Symbols used Safety instructions are marked with symbols The safety instructions are introduced by signal words that express the extent of the hazard e g...

Page 3: ...ignal 1 Close the door The electric locking device is active The alarm signal is turned off If the alarm signal continues 1 Push the key switch to the right and bring it back to the middle position The alarm signal is acknowledged If the alarm signal continues 1 Push and hold the key to the right on the flashing emergency button s key switch 2 Press the emergency button for 1 s and then release 3 ...

Page 4: ...ase of alarm Door open alarm one yellow LED per locking device here 4 connected locks Turn off the alarm signal see Ch 4 6 Emergency button pressed Turn off the alarm signal see Ch 4 6 Alarm system triggered After resetting the fire detector or smoke switch this alarm trigger is automatically reset or Tamper alarm red yellow locked door green yellow unlocked door Check all the connected devices ho...

Reviews: