3 Product description
The STV 1xx is an electromagnetic lock for swing
doors on escape routes and is mounted on the door
frame. Together with a SafeRoute® Control Unit
(SCU), the door lock forms an escape route security
system. The STV 1xx opens without jamming and
without delay. The maximum locking force complies
with Directive for Electrical Locking Systems on
Escape Route Doors (EltVTR).
They may only be mounted on fire and smoke
protection doors, if the usability certificates for these
doors provide for the mounting, and if the related
requirements are followed. Additional notes can also
be found in the notification “Permitted changes and
supplements to fire protection closures” of the
Deutsches Institut für Bautechnik (DIBt), Berlin.
3.1 Variants
The XX markings are color variants. The instructions
are valid for the STV 101 (silver) and STV 111 (white).
3.2 LED displays
LED on
LED off
LED flashes
DCW
®
LED (red)
Bus connection OK
Bus connection interrupted
DCW® error (see SafeRoute®
system instructions)
Config LED (yellow)
Configuration successful
Device not configured
Both LEDs
Configuration mode active
3.3 Technical data
Supply voltage:
24VDC +/- 15%
Retention force
2000 N bei U
nenn
+/- 10 %
Power consumption:
locked: 280mA
unlocked: 20mA
Temperature range:
-10°C to +55°C
Rel. Humidity:
up to 93%
(non condensing)
Degree of protection: IP 30
4 Mounting