8 Complete mounting
1.
Check all gaps. If necessary, adjust the door leaf
in the door frame (Fig. 18).
2.
Check that all the parts provided have been
mounted and that no subsequent modifications
have been made or additional locking devices
added.
3.
Make sure that the locking points are not blocked.
4.
Use a force gauge to measure and record the
actuating forces required to release the escape
door lock. The actuating forces may be max. 70 N
for emergency exit locks according to EN 179, max.
80 N for panic exit locks according to EN 1125.
5.
Clean the masking plate.
6.
This manual must be handed over to the facility
operator and regular maintenance and recording
duties must be observed (see chapter 8).
9 Error messages
LED display
Cause
Action
Power supply outside the tolerance
range (24 V DC +/- 15 %)
Check power supply unit.
Power Reserve function test is faulty
(SVA 2000F only)
Call dormakaba Service.
Unlocking/locking not successful
Check whether the bolt is blocked
from outside the lock. If not, call
dormakaba Service
General error
Disconnect and reactivate the
power supply for the door. If the
error persists, call dormakaba
Service.
SVA-SVI bus connection interrupted
Check correct wiring, especially the
wiring of the SVA and SVI lock.
23
SVI Lock
2019-12
dormakaba Mounting instructions
Complete mounting
WN 059741 45532