7.2 Smoke detector
Fig. 31
SD
Control
Option: Door contact
24V power
supply unit
24V
GND
bu
rd
bk
wh
Wiring of smoke detectors with a SVP 2000/SVP 2000F
8 Complete mounting
1.
Measure the distance between forend and striking
plate (Fig. 32). If necessary, adjust the door leaf or
door frame.
2.
Check that all the parts provided have been
mounted and that no subsequent modifications
have been made or additional locking devices
added.
3.
Make sure that the locking points are not blocked.
4.
Use a force gauge to measure and record the
actuating forces required to release the escape
door lock. The actuating forces may be max. 70 N
for escape doors according to EN 179 and max.
80 N for escape doors according to EN 1125.
5.
This manual must be handed over to the facility
operator and regular maintenance and recording
duties must be observed (see chapter 10).