2 Safety
Fig. 1
Color
Do not damage the product
2.1 Intended use
SVP/SVZ door locks are used to lock doors
automatically and securely each time they are closed.
The SVP door locks can be opened from the panic
side in the escape direction at any time using the
door handle. The SVZ door lock can only be opened
from the inside or outside with the key. Once the
electromagnet is actuated, the handle is engaged
and the door lock can be unlocked on both sides by
operating the handle.
SVZ locks must therefore not be used along escape
routes.
• Only mount combinations of lock and fitting that
have been tested and approved in accordance with
EN 179 or EN 1125. The list of approved components
can be found in the constancy of performance
certificate at www.dormakaba.com. Other
combinations on request.
• Only mount the striking plate supplied. Striking
plates from other manufacturers must be approved
by dormakaba.
• If an SVP door lock with a bolt contact switch is
used for a burglar alarm system, the VdS-certified
bolt contact switch RK from dormakaba (item
no. 15198000) must be used. This is the only way to
ensure that the dead bolt throw functions correctly.
• Panic locks may only be mounted on fire and smoke
protection doors if the usability certificates for
these doors provide for the mounting, and if the
requirements are followed.
• The following SVP door locks are suitable for use
on fire and smoke protection doors: SVP 5000,
SVP 4000, SVP 6000, SVZ 6000, SVP 2000F.
• The SVP 2000 may only be used in fire and smoke
protection doors in combination with the external
Power Reserve module "SVP-PR DCW®" (item no:
70922601).
• If an SVP 2000 or SVP 2000F is operated in
Stand Alone mode in a fire and smoke protection
door, the use of a smoke detector is recommended.
In the event of a fire, it must be ensured that the
locks’ electrical motor controls are disconnected
from the power supply by a smoke detector
provided by the building supervisory authority or
that the control/supply lines to the respective lock
are interrupted. With smoke protection doors, the
smoke detector must respond to the fire parameter
"smoke". The wiring of a smoke detector with
an SVP 2000 or SVP 2000F must be carried out
according to the wiring diagram (see 7.2 on page
19).
2.2 Not intended use
• The lock-case may not be opened by third parties.
If the lock is opened by a third party, there is a risk
that safety-relevant functions (e.g. escape/panic
functions) will no longer exist.
• The identification plate on the lock contains
important information required by law and must
not be damaged or obscured.
2.3 Limitations on use
• Do not make any changes to the door unit that are
not described in this manual.
• If door seals (e.g. profile seals, floor seals) are used,
they must not impede the intended function.
2
SVP/SVZ door locks
2020-03
WN 059744 45532
dormakaba Mounting instructions
Safety