9 Error messages
LED display
Cause
Action
Power supply outside the tolerance
range (24 V DC +/- 15 %)
Check power supply unit.
Power Reserve function test is faulty
(SVA 2000F only)
Call dormakaba Service.
Unlocking/locking not successful
Check whether the bolt is blocked
from outside the lock. If not, call the
dormakaba Service
DCW® bus connection interrupted
Check correct wiring.
CAN bus connection interrupted
Check correct wiring.
General error
Disconnect and reactivate the
power supply for the door. If the
error persists, call dormakaba
Service.
10 Maintenance
Perform the following maintenance steps
at least
once a month
to ensure safe use of the SVP/SVZ door
lock (do not lubricate inside the lockcase):
1.
Check and operate all parts of the door lock.
Ensure that they are fully operational.
2.
Ensure all the parts provided have been mounted
and that no subsequent modifications have been
made or additional locking devices added.
3.
Make sure that the locking points are not blocked.
4.
Use a force gauge to measure and record the
actuating forces required to release the escape
door lock. The actuating forces may be max. 70 N
for escape doors according to EN 179 and max.
80 N for escape doors according to EN 1125.
The actuating forces must not have changed
significantly compared to the measurement after
the initial installation.
5.
Note the date of maintenance, the corrective
actions taken and the name of the person
performing the work.