19
Installation
NOTICE
Before proceeding with Step 12, your installation configuration may involve the installation of
a Swivel MAX at this stage . See Appliance Side Installation Instructions on page 17 . If using
a Swivel MAX at this stage of your configuration, DO NOT PROCEED to the next step if you
have installed a Swivel MAX . Refer to the instructions for that accessory on which step to next
proceed to .
12 . Apply thread sealant (pipe dope) or thread tape to the uninstalled end of the Blue Hose
gas connector .
13 . Hand thread the Blue Hose gas connector end fitting into the female threaded coupling .
Tighten with wrenches .
14 . Reconnect the SnapFast QD or Standard Snap QD nipple to the coupling end by push-
ing the nipple into the coupling end with one hand . For additional instruction on how to
use the SnapFast QD or Standard Snap QD, see page 21 .
15 . Check the tightness of all connections throughout the installation . Tighten with wrenches
as needed .
16 . Perform a leak test in accordance with accepted tested procedures .
17 . Install a restraining cable . Refer to the separate instructions provided with the restraining
cable to install .
18 . Carefully return the gas appliance to its precise operation position . Dormont recom-
mends using Dormont’s Safety-Set to ensure that the appliance does not move during
operation and always returns to the same operating position following service or main-
tenance . Refer to the separate instructions provided with the Safety-Set to install . The
Safety-Set complies with NFPA codes 17A (5 .6 .4 and 96 (12 .1 .2 .3) .
19 . Complete a final inspection of your installation . Refer to the Installation Rights and
Wrongs to ensure that the product is not kinked, bent, or torqued, and check to make
sure that the connector is not caught under the appliance casters .