max. 140 mm
Concealed rough parts for electronic
control elements
– The drywall for the ceiling has to meet quality stardard Q3 (no visible gaps and closed pores).
– The on-site panelling has to be screwed to the mounting bracket of the ceiling installation enclosure for rain panel.
– The weight of the panelling of the ceiling must not put any strain on the mounting bracket of the ceiling installation
enclosure for rain panel. The mounting brackets are only meant to stabilize the rain panel.
– It is recommended to use screws with a drill head to install the panelling to the mounting brackets of the rain panel.
– The mounting brackets have to fall in line with the metal frame of the ceiling structure.
– Any strain from the panelling has to be carried by the metal frame of the dry wall.
– The thickness of the wall covering (tile, stone etc.) in front of the dry wall panelling (gypsum cardboard) around the rough
parts for electronic control elements is min. 7 - max 35 mm.
The installation of the connecting
cable and concealed rough parts for
electronic control elements has to
occur at the same time that the
pre-wall is closed. Wall thickness in
front of the wall panelling:
min. 7 mm - max. 35 mm
Concealed rough parts rain panel +
Hand shower set
Water installation
Water installation - schema
electrical installation
electrical installation - schema
Installation pre-wall
concealed rough Parts for
electronic control elements
Cutouts / anchoring points
Trim installation
Positioning
recommendations
Components
Zones of protection
Pre-wall installation