8.10 UDP connection EcoDose and external control
To use external recipe mode it must be connected to the master controller through an UDP
connection with the “EcoDose control”.
To connect the IF3 interface the X20CP1381 B&R module must be used.
On EcoDose control a UDP server is programmed, the corresponding external control must be
programmed to connect a UDP client.
On the external control the following parameters for the UDP connection must be specified:
-
port number EcoDose control = 2000 remote port
-
IP address EcoDose control = this address must be taken from IF3 interface
Figure 54 System page
-
port number external control = 2001 local port
The IP address of external controller and EcoDose must be in the same subnet.
Subnet mask 255.255.255.0