2.2. 

Pre-assembly requirements

While planning the assembly of the unit consider:

n

ensuring the expliotation conditions of the unit

n

possibility of bringing about ventilation pipes to the device

n

possibility of siphonning of steam condensate

n

possility of bringing about electric energy

n

easy access to maintenance and repairs

Prior  to  connecting  the  unit  check  elements  condition,  including  casing  and  wiring. 
In order to avoid any damage, the unit should be kept in safe place in original packaging. 

EN

Fig.2.

 Flow efficiency characteristics 

First gear

0

50

50

100

100

150

150

250

250

200

200

300

300

350

350

400

3

U[m /h]

400

450

P[Pa]

Luna 350 with 3-gear controller

Second gear

Third gear

2.3. 

Mounting the unit

The unit is destined for assembly under dry roofed rooms with basements (attics, utility room). 
The unit should be assembled in a way to allow free drain condensate from the tub.

Unit  should  be  connected  to  ventilation  ducts  in  accordance  with  designation  on  connectors 
(air inlet, launcher, intake, exhaust). In case of removing the exchanger with tub and replacing 
it, pay attention to tub position - necking which remove condensate from the exchanger must 
be on the side of connectrs air inlet-launcher.

test

Summary of Contents for Luna 350

Page 1: ...el dospel com 48 34 370 30 00 facebook com Dospel Wentylacja Below documentation shall be kept by user In case of not following the conditions of this document the warranty expires MAINTENANCE MANUAL WARRANTY CARD AIR HANDLING UNIT luna 350 rew 22 02 2018 EN test ...

Page 2: ...te 2 5 Conneting to power gird 2 6 Manner of setting anti freeze protection 2 7 Electrical connection scheme 3 STARTING THE UNIT 3 1 General remarks 3 2 Starting the unit 3 3 Use and maintenance 3 4 Exploitation recommendation 4 5 WARRANTY Controller maintenance manual 3 3 4 4 5 5 6 7 7 8 9 9 10 10 11 12 13 2 www dospel com dospel dospel com 48 34 370 30 00 EN CONTENTS luna 350 test ...

Page 3: ... dB Insulation class I International Protection Rating IP X4 Weight 25 60 kg luna 350 3 snapchat dospel com twitter com dospel_com facebook com Dospel Wentylacja 1 MAINTENANCE MANUAL Luna 350 air handling unit is designed to assure air exchange in public utility and apartment buildings The unit s puprose it to supply fresh air from the outside and dispose used air from the rooms with simultaneous ...

Page 4: ...will cause liquefaction of condensate and cumulate it inside and outside of the unit which may cause dampness in the room or damage to the unit WARNING 1 Ventilation installation and other belonging elements must be in accordance with Polish Norms referring to ventilation in residential and public utility buildings 2 The unit is not destined for drying the unseasoned houses 3 In case of damage to ...

Page 5: ...ept in safe place in original packaging EN Fig 2 Flow efficiency characteristics First gear 0 50 50 100 100 150 150 250 250 200 200 300 300 350 350 400 3 U m h 400 450 P Pa Luna 350 with 3 gear controller Second gear Third gear 2 3 Mounting the unit The unit is destined for assembly under dry roofed rooms with basements attics utility room The unit should be assembled in a way to allow free drain ...

Page 6: ...below The pipe should have adequate diameter to the stub pipe 16 mm It shoud be bent into letter U and suffused with water until stabilizing its level Shipon should be palced around 120 mm from the unit and radius should not be less than R 30 mm Given measures should be taken as minimal Unit is sold with siphon and pipe EN The manufacturer suggests mounting acoustic silencers in main ventilation d...

Page 7: ...ner of setting anti freeze protection Luna 350 ventilation unit has been equipped with anti freeze protection heat exchange in the form of a thermostat switching off intake fan This protection is to protect the exchanger from freezing during the occurrence of negative temperatures in winter time In case of occurrence exchanger on the exhaust side of the temperature lower than the set temperature o...

Page 8: ...connector Intake fan 230 170W Exhaust fan 230 170W Intake fan 230 170W Exhaust fan 230 170W Thermostat capillary AIR HANDLING UNIT LUNA 350 Rotation controller Page Electrical connection scheme LUNA 350 WARNING Power supply voltage 230VAC 50hz The current protection should be selected based on the device s power Designed by Checked by connection box test ...

Page 9: ...f the unit prior to connecting it to ventilation WARNING When performing and testing the installation appropriate safety measures must be taken in order to avoid the wrong air flow direction i e from an open flue pipe or other devices with open fire to the room EN 2 7 Electrical connection scheme Fig 7 Manner of connecting 3 gear controller Power cord 2 3x1 5mm Control power supplying cord 2 5x1mm...

Page 10: ...ocations of elements inside the unit manner of filter replacement Fig 9 Summer bypass 3 3 Usage and maintenance WARNING Unit should not work without filters It is only recommended for testing but no longer than 10 minutes When proprely installed unit does not require special maintanance work during use It is recommended to control filters at least once per quarter and change filters It is essentia...

Page 11: ...aminated by solid particles carried by the air over time Periodically check by flushing with water the permeability of the connector Clean if needed Clean inlet and exhaust diffusers if necessary Necessity of filter replacement is signaled by countdown timer via visual warning The filter cartridge made of polyester fabrics cannot be cleaned and must be replaced with a new one if necessary New filt...

Page 12: ...troller made out of white RAL 9002 ABS International Protection Rating IP40 Use Used to turn on off and switching fan s speed Construction Controller is made out of ABS Winder allows immediate possibility of switching fan s speed Assembly It can be assemblied in walls in installation box Nominal power supply voltage V 1 230 AC 2 3 86x86x40 40 IP 40 Nominal current A Number of gears Dimensions mm M...

Page 13: ...nit 6 accidents 7 natural disasters 8 actions of chemical agents 9 action of atmospheric agent discoloration etc 10 improper storage 11 unauthorized repairs 12 transport company 13 improper installation of unit 14 improper exploitation of unit 15 faults resulting from using exploitation materials other than Dospel s 16 faults resulting from using sub assemblies other than Dospel s Warranty exclude...

Page 14: ...ilable a new one with similar parameters can be dispensed in exchange After replecement the warranty period is not extended Warranty is not also exteneded during repair work on the unit Warranty costs 1 Buyer bears transport costs to Dospel main office 2 Dospel bears repair costs 3 When claim is rejected buyer bears diagnostic costs Dospel provides warranty and after warranty service The manner of...

Page 15: ...onsumtion SEC cold climate Specific energy consumtion SEC warm climate SEC range average climate SEC range cold climate SEC range warm climate Device type Type of drive Heat recovery system Thermal efficiency of heat recovery Maximum flow rate Power consumption of fan drive Sound power level L wa Cuperative heat exchanger SWM DSW 3 gear controller Product information according to Commission Regula...

Page 16: ...RL The annual heating saved cold climate The annual heating saved average climate Internal leakage rate The annual heating saved warm climate Flow rate Pressure difference rate Specific power input SPI Not more than 2 Not more than 2 Visual filter change warning signal kWh primary energy year kWh primary energy year kWh primary energy year kWh year Product information according to Commission Regul...

Page 17: ...rev 14 03 2016 luna 350 17 www dospel com dospel dospel com 48 34 370 30 00 EN test ...

Page 18: ...ospel com 48 34 370 30 00 dospel dospel com EN The selective collection of electronic and electric equipment After the period of a given product s exploitation it mustn t be recycled as the unsorted communal waste test ...

Page 19: ...rev 14 03 2016 luna 350 19 www dospel com dospel dospel com 48 34 370 30 00 EN test ...

Page 20: ...tel 48 34 365 98 43 fax 48 34 360 97 00 e mail dospel dospel com www dospel com Dospel reserves the right to introduce any changes regarding its products resulting from ongoing technical development Dospel shall not be liable for printing errors test ...

Reviews: