- 2 -
R20160721
35
78
70
28
8
UNIT : mm
90
40
(Panel Cut-Out : 71mm X 29mm)
L2
L1
100-240Vac,
50/60Hz
1 2
4 5 6
8 9
NTC
COM
FX3S
c
16A, 250Vac
POWER
SUPPLY
NTC
OUT1
+ -
12Vdc
1 2
FX3S-00-T
POWER
SUPPLY
+ -
24Vdc
/ 48Vdc
1 2
FX3S-00-H
POWER
SUPPLY
FX3S
OUT1
Dimensions and Panel Cut-Out Form
Wiring
Constitution
(Function of Display Lamp and Button)
No
Label
Description
1
POWER
100-240Vac, 50/60Hz
2
4
OUT1
(Relay output)
Relay output OUT1 when closed
5
Common signal
6
Relay output OUT1 when open
8
SENSOR
(NTC)
Common signal
9
Temperature sensor input
LED
OUT1
Turn on when output #1 is ON (Flickering at standby)
°C / °F
Celsius / Fahrenheit display units
ON at trip, Flickering at alarm
Parameter set up locked
BUTTON
PRG
Use at program setup
SEL
Execute selected menu or Input setup value
▲
Move between menus & Increase setup value
▼
Move between menus & Decrease setup value
PRG
+
▼
If pushing for 10 sec. at the same time ,
setup value is initialized
Code
Menu
Description / Instructions
Response at
Detection
Reset Type
DEF
Natural defrost
Present temperature and
DEF
message display by turns at natural defrost.
Immediate Stop
Code
Menu
Description / Instructions
Response at
Detection
Reset Type
SYS
Internal
Parameter Error
In Case of change of set value by an unknown case.
Immediate Stop
Automatic Reset
OPN
Sensor Open
In case of Input sensor open wire(Normal operation after sensor connecting)
Immediate Stop
Automatic Reset
SHT
Sensor Short
In case of Input sensor short circuit
Immediate Stop
Automatic Reset
LLL
Lower Input
Lower sensor input than measuring range
Immediate Stop
Automatic Reset
HHH
Higher Input
Higher sensor input than measuring range
Immediate Stop
Automatic Reset
Trip / AlarmLARM MESSAGES
Display Message
※
In case of error occurring, the following messages are flickering at every 0.5 sec. intervals.