background image

PART NO.

FEATURES

WORSID1-N-N

  standard lens, PIR, 24Vac,

  1-pole

WORXID1-N-N

  extended lens, PIR, 24Vac,

  1-pole

WORSID2-DPR-L

  standard lens, PIR, 24Vac,

  2-pole, dimming, photo, 

  relay, low temp.

WORXID2-DPR-L

  extended lens, PIR, 24Vac,

  2-pole, dimming, photo,

  relay, low temp.

WORBID2-DPR-L

  high-bay lens, PIR, 24Vac,

  2-pole, dimming, photo,

  relay, low temp.     

• Commercial grade components for long term reliability

• Straightforward wiring for quick installation

• Factory configured for the most common applications

• DIP switches and dials for advanced functionality

• Options:

Operation

Diversa 24Vac (low voltage) sensors are powered by 24Vac from either the Diversa Series Power Pack (WP-PP20-***) 

or a 24Vac transformer. When in operation, the sensor will detect initial motion using PIR; once motion is detected, 

the sensor and Power Pack (or connected diode pulse relays) contacts will close. Motion through Passive Infrared 

(PIR) is used to maintain the occupied condition as long as occupants remain within coverage pattern of Sensor.

Wiring  Instructions

Wiring to a Power Pack

Black
White

Orange

Sensor

Link

WP-PP20-D

Override / Multi-Level Switching

Black
White

Black
White

Red

Red

Orange

Sw

Sw

(2-pole sensor requires 2-pole Power Pack)

The WOR Series Low Voltage sensors are equipped with #22AWG Leads. Use appropriate sized wire nuts to 

connect the wires to the incoming load terminations. 

Standard, Extended, High-Bay Lens

Dimming, Photo Sensor, Isolated Relay

Low Temperature/High Humidity

DIMENSIONS/MOUNTING inches (mm)

SPECIFICATIONS

3 0° Tilt

4.17”

(106)

0.88”

(2 2)

DIPs and Dials 

under cover 

plate

Wire

Mounting 

ring

Ceiling tile

2.0”

(52)

Power

• 24Vac 

±

 25%

• Class 2 low voltage source

• 60Hz

• Use #18AWG wire

Outputs

• Diode Pulse: Each output is capable of driving up to four Diode

   Pulse relays

• 0-10V Dimming: Connections are polarity-sensitive - up to 25mA 

• Isolated Relay: SPDT Form C contact rated for 1A at 30Vdc

Power Consumption 

• 9.5mA Standard

• 14.0mA with Auxiliary Relay

Approvals

• 

 

FCC

Unit attaches to mounting ring with 

screws or it can be mounted into an 

octogan box.

Environment

• Indoors, stationary, non-vibrating, non-corrosive atmosphere and 

• Ambient Operating Temperature:  32°F to 104°F (0°C to 40°C)
• Storage Temperature:  -14°F to 140°F (-25°C to 60°C)

Octagon Box 

Conduit

The WOR sensor will fit an octagon 
box. It is very important that conduits 
be  attached at opposite ends of the 
box.

Use a 2 1/8 ” or more, deep box. 

If the box is less, use the spacer ring.

non-condensing humidity

sinking

Sensor Location Guidelines

   To optimize the performance of Diversa Sensors, please review the coverage pattern, range, and model to 

match with the application. Room dynamics will change when people and furniture are occupying the space. 

In some rooms, after move in, some sensors may require adjustments.

•  Ensure that the sensor is at least 30 inches away from air handlers/registers and not pointed directly at 

    windows
•  Check that you are installing the right product (check the product model number) as per the drawings

 Sensor Location Guidelines for “P” models

•  Place outside the direct cone of light from fixtures
•  Between 3 to 12 feet from windows
•  As close as possible to the fixture being controlled
•  Above the least illuminated space in the work area
•  Away from lighting that is not being controlled by the sensor

Installation

Standard Lens (S)

• Locate the sensor near the entrance door wall to prevent it from viewing out into the hallway.
• The lens can tilt, allowing the sensor to be pointed toward the area in front of the entrance door.
• Positioning the sensor in this manner ensures that an occupant moves across the longest detection beam 

Typical Enclosed Office

Side View

14  ft

7 ft

0 ft

7 ft

14  ft

9 ft

0 ft

14 ’

12 ’ 10 ’

6’

3’

0’

3’

10 ’

6’

12 ’

14 ’

Top View

Extended Lens for Larger Rooms (X)

• Place the sensor near the center of the room ceiling. Locate it so the approximate distance of 27ft in 

• Tilt the lens to aim the detection zone to the bottom of the door. 
• Positioning the sensor in this manner ensures that the beam does not reach outside the room without

• Optimal usage is to detect large motions such as walking.
• Designed for a mounting height of 7-15ft.

Typical Classroom

27ft

27ft

C

Side View

27  ft

14  ft

0 ft

14  ft

27  ft

9 ft

0 ft

27 ’

16 ’

9’

3’

0’

3’

9’

16 ’

27 ’

Top View

or in dead center of room.

reducing sensitivity.

• Designed for a mounting height of 7-15 ft

upon entrance, utilizing the sensor's maximum PIR range.

High Bay Lens for High Ceiling Applications (B)

• For 15 to 40 foot ceilings
• Position sensor based on ceiling height, beam pattern
and coveage requirements

40  ft

18  ft

0 ft

18  ft

40  ft

40  ft

20  ft

10  ft

0 ft

Side View

40 ’

30 ’

20 ’

10 ’

0’

10 ’

20 ’

30 ’

40 ’

Top View

ON = 

Test M

ode

DIP Switches

Time Delay Dial

Ranges from 30s to 30 min. 

Full turn Clockwise for Auto Time

Full turn Counterclockwise for Test Mode

Light Level Dial

Used to determine light 

level for Photo Functions

Manual Override Button

Grey (-)

Violet (+)

White

Blue

Red

Red/White

Orange

Auto Time LED

Test Mode LED

(Shown with cover

plate removed)

Yellow/White

Yellow Yellow/Black

NC

COM

NO

(Only models with Isolated Relay)

0-10V Dimming

(Only models with Dimming)

Sensor Link

Secondary Output Pole

Primary Output Pole

Return

24Vac

Line Voltage Passive Infrared (PIR) Occupancy / Vacancy Sensor 

Installation Guide

Diversa Occupancy & Vacancy Sensors - Recessed Ceiling, Passive Infrared (PIR), 24Vac  

www.douglaslightingcontrols.com

Diversa by Douglas Lighting Controls

14040200-C                                  