Specifications
Nominal resistance (contaminated)
More than 10,000 ohms
Cable:
Belden #88760 or Alpha #55371
3.6m (12 feet) of gas & oil resistant cable to the inline ISIM
+ 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*:
305 m (1,000 ft.) field wiring
Alarm Threshold Configuration:
Fully Automatic
Diagnostic Reading on Sensor Setup:
0 to 1 (normal) above 5 (in-alarm)
Multi-Drop Restriction
Maximum points per channel = 12 points
924B and DMP Probes = 4 points
ISIM Smart Sensors = 1 point
Devices can be mixed in any combination to hold a maximum of 12
points on one channel
Connections:
Red = Power, Black = Signal, Shield = Ground
NOTE:
*This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the Barrier to each sensor board in the string.
Installation
WARNING:
Make sure you read and fully understand the warnings and
information found in the
Hazardous Areas
section of your console's
Installation Guide before you install or do the servicing of this sensor.
CAUTION:
ALWAYS obey Local and National Electrical Codes applicable to
the installation location.
Make sure that the cables (gas and oil resistant OPW Fuel Management
Systems part # 12-1030) from the field wiring to the controller are in conduit
that is dedicated to intrinsically safe wiring.
Use wire-nuts and epoxy-resin seal-packs for field connections (refer to M00-
390008 Waterproof Electrical Connections for information).
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions
99
Summary of Contents for M2050-PLUS
Page 35: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 35 ...
Page 58: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 58 ...
Page 115: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 115 ...
Page 117: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 117 ...
Page 120: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 120 ...
Page 121: ...M2050 PLUS MagLink LX Plus Installation Manual Dover Fueling Solutions 121 ...
Page 124: ......